Описание

Function Voltage and frequency monitor for generator sets on public grid, international
1- / 3-phase 3
Standard measuring range AC 400 / 230 V
Output contacts 3 s
Operate delay +
Auxiliary voltage required +
Enclosure design Installationsverteiler
Width 70 mm
Type RP 9811
Certificate of conformity (test certificate) of the BG ETEMacc. to VDE-AR-N 4105, DIN VDE 0126-1-1, BDEW-directive,CEI-0-21 Can be used according to EEG 2012 and SysStabV Voltage and frequency monitoring for generator sets Fail-safe 2-channel structure Monitoring of the section switches by measuring the response time System test via test button Enabling inputs allow integration into various ripple control and plantconcepts Isolated grid detection Manual reset Memorising of disconnection time Connection or re-connection after adjustable delay time tOn Factory setting according to:VDE-AR-N 4105, DIN VDE 0126-1-1, BDEW-directive, CEI 0-21,OVE/ONORM, G59/3 LV Random controlled disconnection in the range of 50.2 Hz and 51.5 Hzfor non-regulated power generation systems Random operated connection time (ton) setting range 60...600 s Additional fault signalling relay output High measuring accuracy Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)''