Описание

Function Voltage and frequency monitor for generator sets on public grid acc. to VDE-AR-N 4105
1- / 3-phase 3
Standard measuring range 50 Hz, AC 400 / 230 V
Output contacts 3 w
Operate delay +
Enclosure design Installationsverteiler
Width 70 mm
Type RP 9810
Certificate of conformity (test certificate) of the BG ETEMacc. to VDE-AR-N 4105 Following DIN V VDE V 0126-1-1 Can be used according to EEG 2012 and SysStabV Voltage and frequency monitoring for generator sets >30 kVA onpublic grid, as option also for &le, 30kVA Fail-safe because of 2-channel structure Certificate of conformity (test certificate) of the BG ETEM Monitoring of the section switches with measuring of response time System test via test button Isolated grid detection Manual reset With additional enabling input, e.g. for ripple control receiver Connection or re-connection after adjustable delay time tw Factory setting according to VDE-AR-N 4105 Random controlled disconnection in the range of 50.2 Hz and 51.5 Hzfor non-regulated power generation systems Protection against manipulation by sealable transparent coverover setting switches Additional fault signalling relay output High measuring accuracy Installion type enclosure 4TE (width x height x depth: 70 x 90 x 71 mm)''